Parameter: Scaling COMTRADE
•
Recommended setting value
Scaling COMTRADE
=
Secondary values
With the
Scaling COMTRADE
parameter, you scale the fault record data for the COMTRADE format. Possible
setting values are
Primary values
or
Secondary values
.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2731:1
General:Mode
•
on
•
test
on
Control
_:2761:130
Control:Fault recording
•
with pickup
•
with pickup & AR cyc.
•
user-defined
with pickup
_:2761:131
Control:Storage
•
always
•
with trip
always
_:2761:111
Control:Maximum record
time
0.20 s to 20.00 s
5.00 s
_:2761:112
Control:Pre-trigger time
0.05 s to 4.00 s
0.50 s
_:2761:113
Control:Post-trigger time
0.05 s to 0.50 s
0.50 s
_:2761:116
Control:Manual record time
0.20 s to 20.00 s
0.50 s
_:2761:140
Control:Sampling
frequency
•
8 kHz
•
4 kHz
•
2 kHz
•
1 kHz
2 kHz
Information List
No.
Information
Data Class
(Type)
Type
Binary IO
_:2731:51
General:Mode (controllable)
ENC
C
_:2731:52
General:Behavior
ENS
O
_:2731:53
General:Health
ENS
O
Binary IO
_:2761:300
Control:Start record
SPC
C
_:2761:305
Control:Reset memory
SPC
C
_:2761:306
Control:Clear memory
SPC
C
_:2761:502
Control:>External start
SPS
I
_:2761:503
Control:>Manual start
SPS
I
_:2761:310
Control:Fault number
INS
O
_:2761:311
Control:Recording started
SPS
O
_:2761:314
Control:Record made
SPS
O
_:2761:327
Control:Tmax reduced
SPS
O
3.4.5
3.4.6
System Functions
3.4 Fault Recording
96
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...