Application and Setting Notes
Routings for Activation of the Circuit Breaker
The following image shows the routings needed:
•
The device can execute 3-pole tripping (via the protection device).
•
The device can execute 3-pole opening (via the control).
Furthermore, the device can switch on 3-pole (via the control / AREC)
[loansteu-230311-01.tif, 2, en_US]
Figure 5-25
Activation of the Circuit Breaker
By routing the
Trip/open cmd.
signals to 1 or 2 binary outputs, you can carry out 1, 1.5, and 2-pole activa-
tions of the circuit breaker. You can find a detailed description of this in chapter
i
i
NOTE
Do not confuse these 1-pole, 1.5-pole, and 2-pole activations of the circuit breaker with 1-pole or 3-pole
tripping of the circuit breaker.
Routing for Analysis of the Circuit-Breaker Switch Position
For certain functions of the device, it is useful to detect the circuit-breaker switch position via its auxiliary
contacts. These data are for example:
•
Circuit-breaker position recognition function block
•
Circuit-breaker failure protection function
•
Control function block
The operating principle of the auxiliary contacts is described in the individual functions.
Siemens recommends capturing the
Circuit breaker is open in 3 poles
and
Circuit breaker
is closed in 3 poles
information via auxiliary contacts. This is the optimal configuration for the
control functionality. For purely protection applications, it is also enough to capture just one of the 2 circuit-
breaker positions.
5.5.7.6
Function-Group Types
5.5 Function-Group Type Circuit Breaker, 3-Pole
220
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...