3-Phase Measuring-Voltage Failure
Logic
[losymmet-190912-01.tif, 1, en_US]
Figure 8-7
Logic Diagram 3-Phase Measuring-Voltage Failure
Balanced Fault – VA, VB, VC <
A 3-phase measuring-voltage failure is detected if the following criteria are fulfilled simultaneously:
•
All 3 phase-to-ground voltages drop below the threshold value
3ph.fail. - VA,VB,VC <
•
A jump of the voltage (Signal
jump V
)
If these criteria are fulfilled and the monitoring is released and not blocked, the
3ph.failure-alarm
indica-
tion is output. When the voltage returns (even as 1-phase), the monitoring drops out.
Release by Phase Current
When all phase currents exceed the threshold value
3ph.fail. - phs.curr.release
the monitoring is
released.
Blocking in the Case of a System Incident
In the case of a 3-phase system incident, supervision must be blocked. The device detects a 3-phase incident
with a jump in the current. This change is detected via the internal signal
Jump I
or when the change in
current of a phase current exceeds the threshold value
3ph.fail. - phs.curr. jump
. The change in
8.3.2.4
Supervision Functions
8.3 Supervision of the Secondary System
SIPROTEC 5, High-Voltage Bay Controller, Manual
941
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...