Addr.
Parameter
C
Setting Options
Default Setting
_:102
Swi. seq. #:Check double
activat. blk.
•
no
•
yes
yes
_:103
Swi. seq. #:Time-out
monitoring
•
0
•
1
true
_:104
Swi. seq. #:Monitoring
time
0.02 s to 3600.00 s
30.00 s
_:105
Swi. seq. #:Control
model
•
direct w. normal secur.
•
SBO w. normal secur.
SBO w. normal
secur.
_:106
Swi. seq. #:SBO time-out
0.01 s to 1800.00 s
30.00 s
Switching authority
_:151
Swi. seq. #:Swi.dev.
related sw.auth.
•
0
•
1
false
_:152
Swi. seq. #:Specific sw.
authorities
•
0
•
1
true
_:115
Swi. seq. #:Specific
sw.auth. valid for
•
station
•
station/remote
•
remote
station/remote
_:153
Swi. seq. #:Num. of
specific sw.auth.
2 to 5
2
_:154
Swi. seq. #:Multiple
specific sw.auth.
•
0
•
1
false
Information List
No.
Information
Data Class
(Type)
Type
Swi. seq. #
_:501
Swi. seq. #:>Enable start
SPS
I
_:502
Swi. seq. #:>Enable start (fixed)
SPS
I
_:503
Swi. seq. #:>Start
SPS
I
_:504
Swi. seq. #:>Cancel
SPS
I
_:505
Swi. seq. #:>Successful
SPS
I
_:506
Swi. seq. #:>Failed
SPS
I
_:53
Swi. seq. #:Health
ENS
O
_:302
Swi. seq. #:Execution
ENS
O
_:304
Swi. seq. #:Start
SPC
C
_:305
Swi. seq. #:Cancel
SPC
C
6.5.5
Control Functions
6.5 Switching Sequences
SIPROTEC 5, High-Voltage Bay Controller, Manual
431
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...