Temperature Sensor
Logic
[lotmpval-311012-01.tif, 1, en_US]
Figure 5-79
Logic Diagram of the Temperature Sensor Function Block
Measured Temperature Value
The Temperature sensor function block processes one single measured temperature value delivered from the
RTD unit for the assigned sensor. 12 temperature sensor function blocks are always available in each RTD unit
function (both via Ethernet and serial), even if fewer sensors are connected to the RTD unit.
Various temperature sensor types are supported: Pt100, Ni100, and Ni120 sensors. The function block is noti-
fied regarding the selection of connected type via the
Sensor type
parameter.
The function block delivers a measured temperature value in °C or °F as an output variable. The measured
temperature value is available as an operational measured value and can be monitored by the Temperature
supervision function.
Error Responses
If the measured input value is determined to be incorrect, the quality attribute of the output measured
temperature value is set to
invalid
. The statuses for Health and Error take the statuses in accordance with
the following table:
Table 5-11
Error response
Error Description
Health Status
Error Status
Sensor or line short circuited
Alarm
Yes
Sensor or line interrupted
Alarm
Yes
Measured temperature value
outside the valid measuring range
specified in the technical data. The
valid measuring range depends on
the sensor type.
Alarm
Yes
Sensor not connected
OK
No
Application and Setting Notes
Parameter: Sensor type
•
Default setting
(_:11611:102) Sensor type
=
Pt 100
The
Sensor type
parameter is used to set the sensor element used. You can select between
Pt 100
,
Ni
100
and
Ni 120
.
5.7.7.5
5.7.7.6
Function-Group Types
5.7 Function-Group Type Analog Units
SIPROTEC 5, High-Voltage Bay Controller, Manual
281
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...