AB
Phase C changed over with phase B
i
i
NOTE
If you change the setting value of the parameter
Inverted phases
, consider the following:
The device can take the new setting value only if the binary input signal
>Invert Phases
is not active.
Input signal:
>Phs-rotation reversal
The
>Phs-rotation reversal
binary input is used to switch between the
ABC
phase sequence and the
ACB
phase sequence. The switchover direction depends on the setting of the
Phase sequence
parameter. In
doing so, the phase sequence of all 3-phase measuring points is changed. Changing of the phase-rotation
reversal via the binary input is only possible if no measurands (< 5 % of the rated variables) are present at all 3-
phase measuring points.
Input signal:
>Invert Phases
The binary input
>Invert Phases
is used to activate the setting of the parameter
Inverted phases
. In
doing so, the phase sequence of the selected measuring point is changed. Changing of the phase sequence
via the binary input is only possible if no measurand (< 5 % of the rated variables) is present at the respective
3-phase measuring point.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:101
General:Phase sequence
•
ABC
•
ACB
ABC
General
_:101
VT 3-phase:Rated primary
voltage
0.20 kV to 1200.00 kV
400.00 kV
_:102
VT 3-phase:Rated secon-
dary voltage
80 V to 230 V
100 V
_:103
VT 3-phase:Matching ratio
Vph / VN
0.10 to 9.99
1.73
_:104
VT 3-phase:VT connection
•
3 ph-to-gnd volt. + VN
•
3 ph-to-gnd voltages
•
3 ph-to-ph volt. + VN
•
3 ph-to-ph voltages
3 ph-to-gnd
volt. + VN
_:106
VT 3-phase:Inverted phases
•
none
•
AC
•
BC
•
AB
none
_:111
VT 3-phase:Tracking
•
inactive
•
active
active
_:107
VT 3-phase:Measuring-
point ID
0 to 100
0
7.23.5
Protection and Automation Functions
7.23 Phase-Sequence Switchover
866
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...