Addr.
Parameter
C
Setting Options
Default Setting
_:101
49 Th.overl. #:Threshold
current warning
1 A @ 100 Irated 0.030 A to 35.000 A
1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A
5.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.000 A
5 A @ 50 Irated
0.15 A to 175.00 A
5.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
5.000 A
_:104
49 Th.overl. #:Threshold
thermal warn.
50 % to 100 %
90 %
_:105
49 Th.overl. #:Dropout
threshold operate
50 % to 99 %
90 %
_:112
49 Th.overl. #:Emerg.
start T overtravel
0 s to 15000 s
300 s
_:106
49 Th.overl. #:K-factor
0.10 to 4.00
1.10
_:110
49 Th.overl. #:Thermal
time constant
10 s to 60000 s
900 s
_:111
49 Th.overl. #:Cooling
time constant
10 s to 60000 s
3600 s
_:107
49 Th.overl. #:Imax
thermal
1 A @ 100 Irated 0.030 A to 10.000 A
2.500 A
5 A @ 100 Irated 0.15 A to 50.00 A
12.50 A
1 A @ 50 Irated
0.030 A to 10.000 A
2.500 A
5 A @ 50 Irated
0.15 A to 50.00 A
12.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
2.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
12.500 A
_:108
49 Th.overl. #:Imin
cooling
1 A @ 100 Irated 0.000 A to 10.000 A
0.500 A
5 A @ 100 Irated 0.00 A to 50.00 A
2.50 A
1 A @ 50 Irated
0.000 A to 10.000 A
0.500 A
5 A @ 50 Irated
0.00 A to 50.00 A
2.50 A
1 A @ 1.6 Irated
0.000 A to 1.600 A
0.500 A
5 A @ 1.6 Irated
0.000 A to 8.000 A
2.500 A
_:109
49 Th.overl. #:Tempera-
ture rise at Irated
40 K to 200 K
70 K
_:113
49 Th.overl. #:Storage of
thermal replica
•
no
•
yes
no
_:114
49 Th.overl. #:Behav. at
I> Imax therm.
•
current limiting
•
freeze therm. rep.
current limiting
_:118
49 Th.overl. #:Default
temperature
-55°C to 55°C
40°C
_:117
49 Th.overl. #:Minimal
temperature
-55°C to 40°C
-20°C
_:44
49 Th.overl. #:Tempera-
ture sensor
Setting options depend on
configuration
Information List
No.
Information
Data Class
(Type)
Type
49 Th.overl. #
_:51
49 Th.overl. #:Mode (controllable)
ENC
C
_:500
49 Th.overl. #:>Block stage
SPS
I
7.26.7
Protection and Automation Functions
7.26 Thermal Overload Protection, 3-Phase - Advanced
890
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...