Stage Description
Logic of the Stage
[logisotf-170312-01.tif, 1, en_US]
Figure 7-182
Logic Diagram of the Stage Instantaneous Tripping at Switch onto Fault
Connection of the Stage
The stage is intended to initiate instantaneous tripping when switching onto a fault. To do this, the stage must
be connected to one or more pickups from protection functions or protection stages, for example, to pickup of
an overcurrent-protection stage. That is, the stage of the Instantaneous tripping at switch onto fault func-
tion does not have its own measuring function but requires the pickup of another protection function or
protection stage to pick up.
The stage is active only if switching is pending or executed (for this, see chapter ).
i
i
NOTE
If a protection stage picks up and tripping is blocked by the Inrush-current detection function, the Instan-
taneous tripping at switch onto fault function does not pick up. In this case there is no fault recording
either.
Despite this, if a fault recording is necessary, you can activate it with the parameter
(_:114) Start
flt.rec
of the function Inrush-current detection function (see chapter
Application and Setting Notes
Parameter: Configuration
•
Default setting
(_:5941:102) Configuration
=
no stage
The
Configuration
parameter is used to define with which pickup of a protection function or protection
stage the Instantaneous tripping at switch onto fault function responds.
7.24.3
7.24.4
Protection and Automation Functions
7.24 Instantaneous Tripping at Switch onto Fault
SIPROTEC 5, High-Voltage Bay Controller, Manual
869
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...