has been exceeded. Either the frequency is out of range (10 Hz to 80 Hz) or the input signals are too small for
a manual update. Should this condition occur, the system switches the update frequency to a sampling rate
that corresponds to the rated frequency.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:101
General:Phase sequence
•
ABC
•
ACB
ABC
General
_:8911:101
VT 3-phase:Rated primary
voltage
0.20 kV to 1200.00 kV
400.00 kV
_:8911:102
VT 3-phase:Rated secon-
dary voltage
80 V to 230 V
100 V
_:8911:103
VT 3-phase:Matching ratio
Vph / VN
0.10 to 9.99
1.73
_:8911:104
VT 3-phase:VT connection
•
not assigned
•
3 ph-to-gnd volt. + VN
•
3 ph-to-gnd voltages
•
3 ph-to-ph volt. + VN
•
3 ph-to-ph voltages
•
2 ph-to-ph volt. + VN
•
2 ph-to-ph voltages
•
2 ph-to-gnd volt. + VN
•
2 ph-to-gnd voltages
3 ph-to-gnd
volt. + VN
_:8911:106
VT 3-phase:Inverted phases
•
none
•
AC
•
BC
•
AB
none
_:8911:111
VT 3-phase:Tracking
•
inactive
•
active
active
_:8911:130
VT 3-phase:Measuring-
point ID
0 to 100
0
Voltage transformers1 - 4
_:3811:103
VT 1:Magnitude correction
0.010 to 10.000
1.000
_:3811:108
VT 1:Phase
•
V A
•
V B
•
V C
•
V AB
•
V BC
•
V CA
•
VN
•
Vx
General
_:8881:115
CT 3-phase:CT connection
•
not assigned
•
3-phase + IN
•
3-phase
•
3-phase + IN-separate
•
3-phase, 2 primary CT
•
3ph,2prim.CT + IN-sep
•
2ph, 2p. CT + IN-sep
•
2 phase + IN
3-phase + IN-
separate
5.1.6
Function-Group Types
5.1 Power-System Data
SIPROTEC 5, High-Voltage Bay Controller, Manual
189
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...