dropout according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The
weighted reduction of the time is initiated from 0.9 of the set threshold value.
The characteristic curve and associated formulas are shown in the Technical Data.
Minimum Time of the Curve (Advanced Stage)
With the parameter
Min. time of the curve
, you define the minimum operate delay time. The operate
delay time of inverse-time characteristic curve never falls below the minimum operate delay time.
[Dwocpgr3Mi_20140716-01, 1, en_US]
Figure 7-83
Minimum Operating Time of the Curve
Additional Time Delay (Advanced Stage)
With the parameter
Additional time delay
, you define a definite-time delay in addition to the inverse-
time delay. With this setting, the whole curve is shifted on the time axis by this additional definite time.
Method of Measurement (Basic and Advanced Stage)
You use the
Method of measurement
parameter to define whether the stage uses the
fundamental
comp.
or the calculated
RMS value
.
•
Measurement of the fundamental component:
This method of measurement processes the sampled current values and filters out the fundamental
component numerically.
•
Measurement of the RMS value:
This method of measurement determines the current amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.
Blocking of the Stage (Basic and Advanced Stage)
The following blockings reset the picked up stage completely:
•
Via the binary input signal
>Block stage
from an external or internal source
•
Via the functionality of the
dynamic settings
(see subtitle Influence of other functions via dynamic
settings and chapter
Blocking of the Time Delay (Basic and Advanced Stage)
You can use the binary input signal
>Block delay & op.
to prevent the start of the time delay and thus
also the operate signal. A running time delay is reset. The pickup is indicated and the fault logging and
recording takes place.
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
650
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...