With the binary signal
>Phs-rotation reversal
, you change over the phase sequence of all meas-
uring points.
•
With the binary signal
>Invert Phases
, you change over the phase sequence per measuring point.
The
Inverted phases
parameter available for each measuring point is used to set which phases at the
measuring point must be swapped. The parameter can be found at each 3-phase measuring point.
The 2 binary-signal mechanisms are explained separately below.
Switchover of the Phase Sequence of All Measuring Points
The direction of rotation of the currents and voltages depends on the phase sequence. The following drawing
shows the vector definitions for the 2 phase sequences.
[dwphrdrf-240211-01.tif, 1, en_US]
Figure 7-177
Vector with Different Phase Sequences
The phase sequence of a system or a system section is defined when parameterizing via the
Phase
sequence
parameter. The setting parameter acts on all measuring points.
The operationally induced switchover between the phase sequence
ABC
and the phase sequence
ACB
is initi-
ated via the binary input
>Phs-rotation reversal
. This switches over the phase sequence simultane-
ously at all 3-phase measuring points.
The following image shows a logic diagram for determining the current phase assignment and switchover.
The indications shown on the right show the present phase sequence. If the phase sequence is set via the
Phase sequence
parameter to
ABC
, activation of the binary input will result in a switchover to the phase
sequence
ACB
.
i
i
NOTE
The switchover of the phase sequence is only authorized for a time at which no measured values are
pending. The switchover command must be present for at least 200 ms. The change of phase sequence is
only permissible when the machine is at standstill. If the current and voltage values of all 3-phase meas-
uring points are below 5 % of the rated variables, this is recognized as machine standstill.
A renewed machine standstill must be detected for a resetting of the phase sequence to the set preferred posi-
tion.
Protection and Automation Functions
7.23 Phase-Sequence Switchover
SIPROTEC 5, High-Voltage Bay Controller, Manual
863
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...