Pulse duration connection test
11 μs
Comment:
1
All values in combination with sensors approved by Siemens.
2
Numerical aperture (NA = sin θ (launch angle))
High-Speed Measuring-Transducer Inputs, Voltage/Current (via IO210, IO212)
i
i
NOTE
Current and voltage must not be connected to a measuring-transducer input at the same time; only either
current or voltage may be connected. Due to EMC, no line may be connected to an input that is not used
(current or voltage).
Use shielded cables.
Table 11-1
High-Speed Measuring-Transducer Inputs, Voltage
Differential voltage input channels IO210: 4
27
IO212: 8
28
Measuring range
DC -10 V to +10 V
Fault
< 0.5 % of the measuring range
Input impedance
48 kΩ
Conversion principle
Delta-sigma (16 bit)
Insulation test voltage between the
channels
DC 3.5 kV
Insulation test voltage with respect
to ground/housing
DC 3.5 kV
Max. permissible voltage with
respect to ground on the meas-
uring inputs
300 V
Permissible overload
DC 20 V continuously
DC 60 V continuously (IO210 MT3 terminal point C9)
Measurement repetition
62.5 μs
Insulation class IO210
ELV (Extra Low Voltage) (acc. to IEC 60255-27)
Insulation class IO212
SELV (acc. to IEC 60255-27)
Table 11-2
High-Speed Measuring-Transducer Inputs, Current
Differential current input channels IO210: 4
29
IO212: 8
30
Measuring range
DC -20 mA to +20 mA
Fault
< 0.5 % of the measuring range
Input impedance, current
12 Ω
Conversion principle
Delta-sigma (16 bit)
Permissible potential difference
between channels
DC 3.5 kV
Galvanic separation from ground/
housing
DC 3.5 kV
Permissible current overload
DC 100 mA continuously
27
The IO210 has 4 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
28
The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
29
The IO210 has 4 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
30
The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
Technical Data
11.1 General Device Data
1096
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...