Red error LED
Is activated during the restart
i
i
NOTE
If the fault of defect severity 2 has not be been removed after 3 unsuccessful restarts (reset), the fault is
automatically assigned to defect severity 3. The device will automatically turn to the fallback mode.
Log
For every device error with a subsequent restart (reset), only the restart can be detected in the operational log.
The actual supervision indication is entered in the device-diagnosis log at the point in time of the fault detec-
tion and before the restart. These indications are recorded with a real-time stamp and are thus available for
later analyses. The device-diagnosis log contains expanded fault descriptions. There you also receive recom-
mendations of corresponding corrective measures for each detected device error.
You can find further information on handling the logs in chapter 3.
Overview of Errors
Number
Device-Diagnosis Log
826
Processor error on the base module:
If the fault occurs numerous times, contact the Customer Support Center.
830
FPGA hardware error on the base module:
Contact the Customer Support Center.
834
Memory error (short term):
Reset initiated.
3823
Program run error:
If the fault occurs numerous times, contact the Customer Support Center.
826
CPU overload:
If the fault occurs numerous times, contact the Customer Support Center.
Miscellaneous
Internal firmware error:
If the fault occurs numerous times, contact the Customer Support Center.
Defect Severity 3
Faults of defect severity 3 are fatal device faults that lead to device immediately going into the fallback mode.
The signal
(_:301) Device status
goes to the
Alarm
state. The
Warning
state is not supported for this
signal.
Fatal device errors are errors that cannot be resolved by a restart of the device. In this case, contact the
Customer Support Center. The device goes permanently out of operation, a failure is avoided. In the fallback
mode, minimal operation of the device via the on-site operation panel and DIGSI is possible. In this way, for
example, you can still read out information from the device-diagnosis log.
Life contact
Is terminated in the fallback mode
Red error LED
Is activated in the fallback mode
Log
For every device error that immediately leads to entry into the fallback mode, entries from supervision
messages and from the signal
(_:301) Device status
into the operational log are not possible. The
actual supervision indication is entered in the device-diagnosis log at the point in time of the fault detection,
that is, before entry into the fallback mode. These indications are recorded with a real-time stamp and are thus
available for later analyses. The device-diagnosis log contains expanded fault descriptions. There, you are
offered recommendations of corresponding corrective measures for each detected device error.
You can find further information on handling the logs in chapter 3.
8.8.4
Supervision Functions
8.8 Error Responses and Corrective Measures
988
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...