Measured Values, Two-Winding Transformer
Measured Value Description
Primary
Secondary % Referenced to
V act.
Current, measured positive-
sequence voltage (referenced
to phase-to-phase)
kV
V
Target voltage of the primary
system referenced to the rated
voltage
ΔV act.
Voltage difference between
the target voltage and the
actual voltage
%
%
Voltage difference referenced
to the rated voltage of the
controlled winding
I load
Current measured load current
(positive-sequence system)
A
A
Load current referenced to the
rated value of the function
V max
Maximum positive-sequence
voltage ever measured (refer-
enced to phase-to-phase)
kV
V
Maximum voltage of the
winding referenced to the
rated voltage of the winding
V min
Minimum positive-sequence
voltage ever measured (refer-
ence to phase-to-phase)
kV
V
Minimum voltage of the
winding referenced to the
rated voltage of the winding
V target
Calculated target voltage with
consideration of Z compensa-
tion
kV
V
Target voltage of the winding
referenced to the rated voltage
of the winding
PhAng
Phase angle of the currently
measured load current
°
°
-
I load Σ
Sum of the currently measured
load currents. Active when line
compensation is activated.
A
A
Load current referenced to the
rated current of the function
I circul.
Currently measured circulating
reactive current
A
A
Circulating reactive current
Vact.m
Currently measured control
voltage
kV
V
Current voltage of the control
referenced to the rated voltage
of the function
ΔVactV
Voltage difference
%
%
Voltage difference referenced
to the rated voltage of the
function
ΔVactC
Voltage difference
%
%
Voltage difference referenced
to the rated voltage of the
function
The function measured values V max and V min can be reset with the input indication
>Reset min./max.
.
For the two-winding transformer, you can find the measured values under the following menu entries of the
device:
•
Main menu → Measurements → Voltage control 2w → 90V V.contr.2w
•
Main menu → Measurements → Voltage control 2w → Statistics → 90V V.contr.2w
Measured Values for Parallel Control, Proxy
Measured Value Description
Primary
Secondary % Referenced to
V act.
Actual voltage of winding
kV
V
Target voltage of the primary
system referenced to the rated
voltage of the function
1/X trf.
Susceptance, internal value for
GOOSE transmission
1/Ω
I load
Load current
A
-
Load current referenced to the
rated current of the function
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual
485
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...