[loaweext-140212-01.tif, 1, en_US]
Figure 7-54
Connection of an External Automatic Reclosing Function
There are no setting parameters for operation with external automatic reclosing functions. The function
provides exclusively the following described binary inputs. The external reclosing device can thus have an
influence on the effects of the internal protection functions.
The following connection possibilities exist:
•
From the external reclosing function, the signal
>Release stages
can be coupled so that the protec-
tion functions use special stages or zones for release. An example is the release of an overreaching zone
with a distance protection or the non-delayed tripping of an overcurrent protection stage in the 1st
reclosing cycle.
•
For applications with 1-pole tripping, the external reclosing can provide the signal
>1-pole trip
permitted
, based on which the protection functions can switch off the 1-pole circuit breaker.
•
For applications with reclosing functions only with 1-pole faults and stage or zone releases through the
reclosing function can the signal
>1-pole AR only
be connected. The protection functions use this
information to allow the stage or zone release only affect 1-pole faults.
Information List
No.
Information
Data Class
(Type)
Type
Ext
_:6661:51
Ext:Mode (controllable)
C
_:6661:501
Ext:>Release stages
I
_:6661:502
Ext:>1-pole trip permitted
I
_:6661:503
Ext:>1-pole AR only
I
_:6661:52
Ext:Behavior
O
_:6661:53
Ext:Health
O
_:6661:54
Ext:Inactive
O
7.2.6.2
Protection and Automation Functions
7.2 Automatic Reclosing Function
584
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...