Underfrequency-Protection Stage
Logic of a Stage
[lostufqp-040411-01.tif, 2, en_US]
Figure 7-159
Logic Diagram of the Underfrequency-Protection Stage
Frequency-Measurement Method
Underfrequency protection is available in 2 functional configurations. These work with different frequency-
measurement methods. You select the frequency-measurement method in dependence of the application.
•
Angle-difference method (method A):
The angle-difference method determines the phasor of the positive-sequence voltage in multiphase
systems. In the case of 1-phase connection, it always processes the phasor of the connected voltage.
Since the change of angle of the voltage phasor over a given time interval is proportional to the
frequency change, the current frequency can be derived from it.
•
Filtering method (method B):
The filtering method processes the instantaneous voltage values and determines the current frequency
using a suitable combination of filters. The frequency-protection function selects automatically the
largest voltage as the measurand. In a multiphase connection, the phase-to-phase voltage is always the
largest. If in a multiphase connection the selected voltage is no longer available, the function changes
over automatically to the next maximum voltage. The function can even operate with just one voltage.
7.19.3
Protection and Automation Functions
7.19 Underfrequency Protection
830
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...