FUNCTION

 

 

Series S001 and S002 circulation units 
are applied to the primary circuit of 
solar systems and oversee management 
of the solar panel - storage tank fluid 
thermodynamic cycle for subsequent 
supply to utilities via hydraulic 
distribution circuits. 
They consist essentially of a circulator 
with appropriate performance (rate of 
flow/head) and regulation and control 
devices governing the operating circuit.

 

Technical Information Sheet 07/2013 - ENG

 

 
 
 
 
 
 
 
   
 
 

 
 

TECHNICAL FEATURES 

 

Fluid used:   

 

      Water, glycol solutions 

                                                               (glycol 25%÷50% max) 

Permitted temperature range: 

     

-10 °C / +160°C 

Max. ambient temperature: 

     

+40°C 

Max. operative pressure: 

     

10 bar 

Min. pressure on intake 
opening with temperatures of:   

   

+50 °C     :    0,05 bar 

 

 

 

     

+95 °C     :      0.3 bar 

  

 

 

      +110 °C   :         1 bar 

Min. pressure for opening on/off 
and check valve:                            

p:2Kpa (200 mm c.a.) 

 

Safety valve 

 

Calibration of safety valve:  

      

6 bar 

Safety  valve temperature range:

   

-30÷160°C 

Connections of safety valves: 

      

1/2" F 

 

Further information 

 

Manometer scale: 

 

       0÷6 bar 

Thermometer scale:   

      

0÷160 °C 

System connections:   

       3/4” M 

Connection with expansion tank:   3/4” M 
Filling/emptying connections 
with hose connection:

                 

Ø 13 mm 

 

Component materials 

 

Body 

 

 

      Brass EN 12165 CW617N 

Thermometer 

 

      Steel/Alluminium 

Seals 

 

 

      PTFE 

Sealing elements 

 

      EPDM-Perox 

Flat seals   

 

      Betaflex 

Insulation shell 

 

      PPE, Conducibility 

λ

(

T):   

 

 

   

 

      0.041 (W/mK) 

 
 
 
 
 
 

Art.S001-S002 SOLAR MODULE WITH 
DELIVERY AND RETURN CONNECTIONS

Pump model:  -  Wilo      “Solar ST20/6” 
                         - Grundfos  “Solar 15-65”

 

Centre-to-centre distance:         130 mm 
Electrical power supply:            230V - 50Hz 
Operatine temperature:             -10°C÷110°C c.a. 
Max. temperature:                     140°C for max 2 hours  
Max. operating pressure:           10 bar 
Protection level:                         IP 44 

Art.S001 

Art.S002 

Pump hydraulic features 

Grundfos “Solar 15-65” 

Water flow (m

3

/h)   (1, 2, 3 = Fast pump)

 

Pump hydraulic features 

Wilo “Solar ST20/6” 

Summary of Contents for S001

Page 1: ...95 C 0 3 bar 110 C 1 bar Min pressure for opening on off and check valve p 2Kpa 200 mm c a Safety valve Calibration of safety valve 6 bar Safety valve temperature range 30 160 C Connections of safety...

Page 2: ...urn connection with Anti gravity non return valve 5 Wilo Solar ST20 6 o Grundfos Solar 15 65 circulation pump 6 Flow controller with on off valve return connection 7 On off valve with built in thermom...

Page 3: ...4 08 about art S301 and S302 FILLING THE SYSTEM 1 Open the on off valve connected with the air bleed valve A Fig 1 located at the highest point of the system 2 Open the on off and check valves turning...

Page 4: ...point in the system A Fig 1 and in the air separator 8 in Tab 1 When you have finished bleeding air check the pressure in the system and restore the desired operating pressure if necessary EMPTYING TH...

Page 5: ...ng the rate of flow of fluid circulating in the system The flow meter has a rate of flow limiter which may be adjusted manually with a screwdriver Fig 4 A rate of flow indicator present inside the mea...

Page 6: ...ses are separated from the head conveying fluid and accumulate in the upper part of the deaerator During start up accumulated gases must be evacuated periodically during the day using the manual air b...

Page 7: ...rised personnel familiar with the instructions contained herein Make sure the system is shut down before performing any work on it ELECTRICAL CONNECTIONS Electrical connections must be made by qualifi...

Page 8: ...ICMA s p a via Garavaglia 4 20012 Cuggiono MI ITALY Tel 39 02 97249134 39 02 97249135 Fax 39 02 97241550 www icmaspa it e mail sales icmaspa it pag 8...

Reviews: