Addr.
Parameter
C
Setting Options
Default Setting
_:108
(3-pole circuit
breaker)
50BF Ad.CBF #:Retrip
after T1
•
no
•
start T2 after T1
•
parallel start T2, T1
no
_:103
50BF Ad.CBF #:CB
aux.cont. crit. allowed
•
no
•
w. 'CB pos. closed 3p.'
•
w. 'CB pos. closed Lx'
no
_:104
50BF Ad.CBF #:Dropout
•
with effective criterion
•
w. aux.c. and curr.crit.
with effective
criterion
_:110
(1/3-pole
circuit
breaker)
50BF Ad.CBF #:Retrip
after T1
•
no
•
start T2 after T1
•
parallel start T2, T1
no
_:110
(3-pole circuit
breaker)
50BF Ad.CBF #:Delay T2
for 3-pole trip
0.050 s to 60.000 s
0.130 s
_:109
(1/3-pole
circuit
breaker)
50BF Ad.CBF #:Retrip
1-/3-pole
•
3-pole
•
1-pole
3-pole
_:109
(3-pole circuit
breaker)
50BF Ad.CBF #:Delay T1
for 3-pole retrip
0.000 s to 60.000 s
0.050 s
_:102
50BF Ad.CBF #:Threshold
phase current
1 A @ 100 Irated 0.030 A to 35.000 A
0.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
2.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
2.500 A
_:101
50BF Ad.CBF #:Threshold
sensitive
1 A @ 100 Irated 0.030 A to 35.000 A
0.250 A
5 A @ 100 Irated 0.15 A to 175.00 A
1.25 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.250 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
1.250 A
_:111
(1/3-pole
circuit
breaker)
50BF Ad.CBF #:Delay T1
for 3-pole retrip
0.000 s to 60.000 s
0.250 s
_:111
(3-pole circuit
breaker)
50BF Ad.CBF #:Sup.time
for release signl
0.00 s to 1.00 s
0.06 s
_:113
(1/3-pole
circuit
breaker)
50BF Ad.CBF #:Delay T1
for 1-pole retrip
0.000 s to 60.000 s
0.050 s
_:112
(1/3-pole
circuit
breaker)
50BF Ad.CBF #:Delay T2
for 3-pole trip
0.050 s to 60.000 s
0.130 s
_:112
(3-pole circuit
breaker)
50BF Ad.CBF #:Minimum
operate time
0.00 s to 60.00 s
0.10 s
Protection and Automation Functions
7.1 Circuit-Breaker Failure Protection
538
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...