Information List
No.
Information
Data Class
(Type)
Type
User curve #
_:81
User curve #:>Block stage
SPS
I
_:84
User curve #:>Activ. dyn. settings
SPS
I
_:500
User curve #:>Block delay & op.
SPS
I
_:54
User curve #:Inactive
SPS
O
_:52
User curve #:Behavior
ENS
O
_:53
User curve #:Health
ENS
O
_:60
User curve #:Inrush blocks operate
ACT
O
_:62
User curve #:Dyn.set. AR cycle1act.
SPS
O
_:63
User curve #:Dyn.set. AR cycle2act.
SPS
O
_:64
User curve #:Dyn.set. AR cycle3act.
SPS
O
_:65
User curve #:Dyn.set. ARcycl.>3act
SPS
O
_:66
User curve #:Dyn.set. CLP active
SPS
O
_:67
User curve #:Dyn.set. BI active
SPS
O
_:68
User curve #:Dyn. set. blks. pickup
SPS
O
_:59
User curve #:Disk emulation running
SPS
O
_:55
User curve #:Pickup
ACD
O
_:56
User curve #:Operate delay expired
ACT
O
_:57
User curve #:Operate
ACT
O
Blocking of the Tripping by Device-Internal Inrush-Current Detection
Description
With the
Blk. w. inrush curr. detect.
parameter, you can define whether tripping of the stage
should be blocked when a threshold value is exceeded due to an inrush current. In case of a blocking, the
stage picks up. The start of the tripping delay and the trip signal are blocked. The function signals this through
a corresponding indication. If the blocking drops out and the threshold value of the stage is still exceeded, the
time delay is started. After that time, the stage operates. The following figure only shows the part of the stage
(exemplified by definite-time overcurrent protection stage 1) that illustrates the influence of the blocking.
Only if the central function Inrush-current detection (see chapter
11.12 Inrush-Current Detection
can the blocking be set.
7.4.6.4
7.4.7
7.4.7.1
Protection and Automation Functions
7.4 Overcurrent Protection, Phases
628
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...