Data Substitute Values
Depending on the data type, different data substitute values must be used.
Data Type
Possible Data Substitute Values
ACD, ACT
general
0 (False), 1 (True)
(The directional information is always manually updated with
unknown
.
PhsA, phsB, phsC, and neut are manually updated with the same
value just like how the general value is set.)
BAC, APC
mxVal
Floating-point range and range of values according to IEEE 754
(single precision)
BCR
actVal
–2
63
to 2
63
– 1
CMV
mag, ang
Floating-point range and range of values according to IEEE 754
(single precision)
DPC, DPS
stVal
0, 1, 2, 3 (intermediate-state, off, on, bad-state)
INC
stVal
–2 147 483 648 to 2 147 483 647
INS
stVal
–2 147 483 648 to 2 147 483 647
ISC, BSC
valWTr.posVal
–64 to 64
valWTr.transInd
0 (False), 1 (True)
SPC, SPS
stVal
0 (False), 1 (True)
MV
mag
Floating-point range and range of values according to IEEE 754
(single precision)
For controllable types, the following substitute values apply in addition to the settable state values or meas-
ured values:
ctlNum
=
0
stSeld
=
False
origin.orIdent =
Substituted by quality processing
origin.orCat
=
AUTOMATIC_BAY
Previous Quality Processing/Affected by the User for Received GOOSE Values
In the Information Routing editor, you can influence the data value and quality of all data types. The
following figure shows the possible influence using the example of a DPC data type.
•
In the DIGSI 5 project tree, double-click Information Routing.
•
Select the desired signal in the External Signals group.
•
Open the Properties window and select the Processing Quality Attributes sheet.
System Functions
3.3 Processing Quality Attributes
SIPROTEC 5, High-Voltage Bay Controller, Manual
81
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...