Reading on the Device through the On-Site Operation Panel
•
To reach the communication log from the main menu, use the navigation keys on the on-site operation
panel.
Main Menu → Test & Diagnosis → Log → Communication log
•
You can navigate within the displayed indication list using the navigation keys (up/down) on the on-site
operation panel.
Figure 3-19
Reading the Communication Log on the On-Site Operation Panel of
the Device
Deletability
The communication logs of your SIPROTEC 5 device can be deleted. Read details about this in chapter
3.1.6 Saving and Deleting the Logs
Configurability
The communication logs are not freely configurable. The entries are preconfigured.
Motor-Starting Log
The motor-starting log records the starting current, starting voltage and the start duration each time a motor
starts. The motor-starting current and the motor-starting voltage are displayed as primary values. Up to 200
indications can be stored in the motor-starting log.
Measurement of the motor statistics starts when the motor state changes to
Start
. Measurement of the
motor starting time ends as soon as the motor state changes to
Standstill
or
Running
. The motor state is
obtained from the Motor-state detection function.
No entry is recorded in the motor-starting log if the motor state changes to
Start
and the current drops
below the motor starting current within 500 ms.
Table 3-6
Motor-Starting Log
Measured Values
Primary
Start duration
Motor starting time
s
Starting current
Motor-starting current (primary)
A (or kA)
Starting voltage
Motor-starting voltage (primary)
V (or kV)
Reading from the PC with DIGSI 5
•
Use the project-tree window to reach the motor-starting log of your SIPROTEC 5 device.
Project → Device → Device Information → Log → Motor-starting log
The state of the motor-starting log last loaded from the device is shown to you.
3.1.5.10
System Functions
3.1 Indications
66
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...