Arc Protection
Setting Values
Threshold I>
1 A @ 100 Irated
0.030 A to 35.000 A
Increments of 0.001 A
5 A @ 100 Irated
0.15 A to 175.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
Increments of 0.001 A
Threshold 3I0>>
1 A @ 100 Irated
0.030 A to 35.000 A
Increments of 0.001 A
5 A @ 100 Irated
0.15 A to 175.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
Increments of 0.001 A
External trip initiation
no
current
light
Operating mode
light only
current and light
Sensor
point sensor
line sensor
custom
Threshold light
-28.00 dB to 0.00 dB
Increments of 0.01
Channel
Possible settings, application-dependent
Dropout
The larger dropout differential (=
| pickup threshold – dropout threshold |
) of the following
2 criteria is used:
Dropout differential derived from the
Dropout ratio
parameter
If this parameter is not available, a dropout ratio of 95 % applies to the overcurrent protection and a dropout
ratio of 105 % applies to the undercurrent protection.
Minimum absolute dropout differential
Protection-class current transformers
15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument transformers
0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Times
Shortest operate time
Operating mode = light only
Approx. 2.6 ms + OOT
89
Shortest operate time
Operating mode = Current and light
Approx. 4.0 ms + OOT at 50 Hz
Approx. 3.8 ms + OOT at 60 Hz
11.35
89
Technical Data
11.35 Arc Protection
1180
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...