Measured Values
Primary Secon-
dary
% Referenced to
V
AB
, V
BC
, V
CA
Phase-to-phase voltages
kV
V
Rated operating voltage of the primary values
V
0
Zero-sequence voltage
kV
V
Operating rated voltage of primary values/√3
V
NG
Neutral-point displacement
voltage
kV
V
Operating rated voltage of primary values/√3
f
Frequency
Hz
Hz
Rated frequency
P
total
Active power
(total power)
MW
W
Active power of the primary values
√3 · V
rated
· I
rated
Q
total
Reactive power
(total power)
Mvar
var
Reactive power of the primary values
√3 · V
rated
· I
rated
S
total
Apparent power
(total power)
MVA
VA
Apparent power of the primary values
√3 · V
rated
· I
rated
Cos φ
Active power factor
(abs)
(abs)
100 % corresponds to cos φ = 1
P
A
, P
B
, P
C
Phase-related active power
MW
W
Active power of the phase
V
rated phsx
· I
rated phsx
Q
A
, Q
B
, Q
C
Phase-related reactive power
Mvar
var
Reactive power of the phase
V
rated phsx
· I
rated phsx
S
A
, S
B
, S
C
Phase-related apparent power
MVA
VA
Apparent power of the phase
V
rated phsx
· I
rated phsx
The operational measured values are explained in more detail in chapter
9.3 Operational Measured Values
.
Output Logic
The output logic treats the pickup and trip signals of the protection and supervision functions that are avail-
able in the function group separately, in a pickup logic and a trip logic, respectively. The pickup and trip logic
generate the overreaching indications (group indications) of the function group. These group indications are
transferred via the Protection information interface to the Circuit-breaker function group and are processed
further there.
The pickup signals of the protection and supervision functions in the Voltage-current 3-phase function group
are combined in a phase-selective manner and output as a group indication.
[lo_anrlin, 3, en_US]
Figure 5-5
Creation of the Pickup Indication of the Voltage-Current 3-Phase Function Group
The trip signals from the protection and supervision functions of the Voltage-current 3-phase function group
always result in 3-pole tripping of the device.
Function-Group Types
5.2 Function-Group Type Voltage/current 3-Phase
196
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...