RAXN-LCD

                      Network Remote Annunciator Panel

LT-895    Rev  3 

Feb 2018

Installation and Wiring Manual

MGC Network

Fire     Control     System

-     System      Normal    -

Feb   21,  2018       2:21   PM

SIGNAL

SILENCE

FIRE

DRILL

SYSTEM

RESET

GENERAL

ALARM

ACKNOW-

LEDGE

LAMP

TEST

ENTER

TROUBLE

QUEUE

SUPV.

QUEUE

ALARM

QUEUE

MENU

CANCEL

INFO

MONITOR

QUEUE

A.C.

ON

PRE-

ALARM

GROUND

FAULT

Summary of Contents for RAXN-LCD

Page 1: ...llation and Wiring Manual MGC Network Fire Control System System Normal Feb 21 2018 2 21 PM SIGNAL SILENCE FIRE DRILL SYSTEM RESET GENERAL ALARM ACKNOW LEDGE LAMP TEST ENTER TROUBLE QUEUE SUPV QUEUE ALARM QUEUE MENU CANCEL INFO MONITOR QUEUE A C ON PRE ALARM GROUND FAULT ...

Page 2: ......

Page 3: ...roduction 1 2 0 Installation Instructions 2 3 0 Jumper Settings 3 4 0 DIP Switch Settings 4 5 0 Wiring Instructions 5 6 0 Cable Connections 6 7 0 Specifications 7 8 0 Battery Calculations 8 9 0 Warranty and Warning Information 9 ...

Page 4: ......

Page 5: ...he RAXN LCD may be mounted in the BB 1000 MMX BB 1000 Series backboxes the BB 5008 BB 5014 BBX FXMNS MMX BBX FXMNS and FX LOC MMX LOC enclosures IPS 2424DS Programmable Input Switches 2 Frames QAZT 5302DS Zoned Paging and Telephone Selector 1 Frame QMT 5302N Master Telephone 1 Frame QMP 5101N Master Paging 1 Frame QMP 5101NV Master Paging 1 Frame QMT 5302NV Master Telephone 1 Frame FDX 008W KI Fan...

Page 6: ...UNTED WITH STANDARD 4 X 4 ELECTRICAL BOXES BB 1001D R BACKBOX IS SHOWN RAXN LCD ANNUNCIATOR GB 1001RAXN GUARD BRACKET B 12 75 H A 6 32 HEXNUTS 1 85 WALL DOOR BACKBOX BACKBOX MODEL HEIGHT OF BACKBOX H IN WIDTH OF BACKBOX IN HORIZONTAL MOUNTING HOLE DIM A IN VERTICAL MOUNTING HOLE DIM B IN BB 1001D R MMX BB 1001D R 9 0 12 75 9 95 7 5 BB 1002D R MMX BB 1002D R 18 0 12 75 9 95 16 5 BB 1003D R MMX BB 1...

Page 7: ...er modules beyond the first 13 frames Refer to the Fire Alarm Panel manual for further details RS 485 TERMINALS 24V POWER TERMINALS SW1 LCD Display Contrast Adjust P5 P6 P7 P5 connects to first set of display modules up to a total of 13 frames P6 is an expansion connector for the next 14 frames and P7 for the next 14 frames beyond that for a total of 41 frames RS 232 Port for Printer Connection Ju...

Page 8: ... as to whether addresses 37 to 39 are available 37 ON OFF ON OFF OFF ON 38 OFF ON ON OFF OFF ON 39 ON ON ON OFF OFF ON RAXN LCD Remote Annunciator Address Setting DIP SWITCH SW1 SW1 1 8 DIP SWITCH SETTINGS ON OFF DIP switch SW1 is used to set the address of the RAXN LCD DIP switches are for assigning an address to the RAXN LCD Binary addresses 33 to 39 are available with the least significant bit ...

Page 9: ...ping is allowed Each RAXN LCD Shared Display has a 120 ohm end of line resistor on its RS 485 output terminals This resistor is removed on all except the last wired annunciator 24V DC Wiring The 24 VDC field wiring needs to be of an appropriate gauge for the number of annunciators and the total wiring run length Refer to the Current Drain for Battery Calculations on page 8 to calculate the maximum...

Page 10: ...CE GENERAL ALARM ACKNOW LEDGE FIRE DRILL SYSTEM RESET LAMP TEST on the RAXN LCD Annunciator P5 Connects to the RAX 1048TZDS 48 LED Annunciator module This connector may connect up to 13 frames of display modules P6 Connects to next 14 frames i e frame 15 to 27 of display modules P7 Connects to next 14 frames i e frame 28 to 41 of display modules Terminals Terminal wiring is required for the RS 485...

Page 11: ... are 18GA BB 1003D R MMX BB 1003D R is 16 GA CRS BB 1008D R MMX BB 1008D R BB 1012D R MMX BB 1012D R backboxes are 16 GA CRS Doors are 14 GA See Installation Instructions on page 6 for enclosure dimensions Other larger enclosures available are BB 5008 BB 5014 BBX FXMNS MMX BBX FXMNS and FX LOC MMX LOC Annunciator Models RAXN LCD Remote Network Shared Display LCD Annunciator 24V DC nominal Intercon...

Page 12: ... 10mA _______ number of RAX 1048TZDS number of IPS 2424DS Maximum Alarm Current 164 mA ___________ x 35 mA ___________ x 15mA _______ number of RAX 1048TZDS number of IPS 2424DS The Normal Standby Current is used for battery size calculations see the Network Fire Alarm Manual for battery calculations and includes the current drain for the Trouble Buzzer Trouble LED and one alarm LED The Maximum Al...

Page 13: ...ife insurance Nor is the system a substitute for property owners renters or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation Building automation systems produced by the Mircom Group of Companies are not to be used as a fire alarm or life safety system NOTE TO INSTALLERS All Mircom Systems have been carefully designed to be as effective as possib...

Page 14: ...s may not provide timely warning of fires caused by carelessness or safety hazards such as smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical circuits or children playing with matches or arson 10 Power Failure Some Mircom System components require adequate electrical power supply to operate Examples include smoke detectors beacons HVAC and ...

Page 15: ...s Alarm notification appliances such as sirens bells horns or strobes may not warn or waken a sleeping occupant if there is an intervening wall or door It is less likely that the occupants will be alerted or awakened when notification appliances are located on a different level of the residence or premise 17 Software Malfunction Most Mircom Systems contain software No warranties are provided as to...

Page 16: ... ON L4K 5W3 Tel 888 660 4655 905 660 4655 Fax 905 660 4113 MGC 2018 Printed in Canada Subject to change without prior notice www mircom com U S A 4575 Witmer Industrial Estates Niagara Falls NY 14305 Tel 888 660 4655 905 660 4655 Fax 905 660 4113 ...

Reviews: