Operational Measured Values
Operational measured values are assigned to different function groups.
The values can be displayed as primary and secondary values and as percentage values.
The operational measured values are calculated according to the following definition equations:
RMS values
Active power
Apparent power
Reactive power
n
φ
n
Harmonic order
The angle difference between the voltage and current of the nth harmonic
Power factor
Active power factor
Voltage/Current 3-Phase Function Group
The following table describes the operational measured values of the 3-phase voltage/current function
group.
All protection functions have access to the values.
Table 9-1
Operational Measured Values of the Voltage/Current 3-Phase Function Group
Measured Values
Primary
Secon-
dary
% Referenced to
I
A
, I
B
, I
C
Phase currents
A
A
Rated operating current of the primary values
3I0
Calculated zero-sequence
current
A
A
Rated operating current of the primary values
I
N
Neutral-point phase current
A
A
Rated operating current of the primary values
V
A
, V
B
, V
C
Phase-to-ground voltages
kV
V
Rated operating voltage of primary values/√3
V
AB
, V
BC
, V
CA
Phase-to-phase voltage
kV
V
Rated operating voltage of the primary values
V
0
Calculated zero-sequence
voltage
kV
V
Rated operating voltage of primary values/√3
V
N
Measured neutral-point
displacement voltage
kV
V
Rated operating voltage of primary values/√3
f
Frequency
Hz
Hz
Rated frequency
P
Active power
(total power)
MW
–
Active power of the primary values
√3 · V
rated
· I
rated
Q
Reactive power
(total power)
Mvar
–
Reactive power of the primary values
√3 · V
rated
· I
rated
S
Apparent power
(total power)
MVA
–
Apparent power of the primary values
√3 · V
rated
· I
rated
9.3
Measured Values, Energy Values, and Supervision of the Primary System
9.3 Operational Measured Values
SIPROTEC 5, High-Voltage Bay Controller, Manual
997
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...