Absolute pickup value
1 A @ 50 and 100 Irated
0.000 A to 35.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.00 A to 175.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.000 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.000 A to 8.000 A
Increments of 0.001 A
Dropout
Disk emulation
Instantaneous
–
Time multiplier
0.05 to 15.00
Increments of 0.01
Number of value pairs for the operate curve
2 to 30
Increments of 1
X values of the operate curve
1.00 p.u. to 20.00 p.u.
Increments of 0.01 p.u.
Y values of the operate curve
0.00 s to 999.00 s
Increments of 0.01 s
Number of value pairs for the dropout characteristic
curve
2 to 30
Increments of 1
X values of the dropout characteristic curve
0.05 p.u. to 0.95 p.u.
Increments of 0.01 p.u.
Y values of the dropout characteristic curve
0.00 s to 999.00 s
Increments of 0.01 s
Additional time delay
0.00 s to 60.00 s
Increments of 0.01 s
Dropout
The greater dropout differential (=
| pickup value – dropout value |
) of the following 2 criteria
applies:
Dropout
95 % of 1.1 ⋅ threshold value or 95 % of the absolute
pickup value
Minimum absolute dropout differential
Protection-class current transformer
15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer
0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Reset of the Integration Timer
Instantaneous
With dropout
Disk emulation
Approx. < 0.90 ⋅ threshold value
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1
According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz
f > 80 Hz
Active
Tolerances
Currents, method of measurement = fundamental
component
1 % of the setting value or 5 mA (I
rated
= 1 A)
or 25 mA (I
rated
= 5 A), (f
rated
± 10 %)
Currents, method of measurement = RMS value, no filter applied
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic
1 % of the setting value or 5 mA (I
rated
= 1 A)
or 25 mA (I
rated
= 5 A), (f
rated
± 10 %)
Technical Data
11.8 Overcurrent Protection, Phases
SIPROTEC 5, High-Voltage Bay Controller, Manual
1121
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...