Addr.
Parameter
C
Setting Options
Default Setting
_:5131:106
Device combin.:Address of
device 5
1 to 65534
105
_:5131:107
Device combin.:Address of
device 6
1 to 65534
106
_:5131:101
Device combin.:Local
device is device
1 to 6
1
_:5131:122
Device combin.:Lowest
appearing bit rate
•
64 kBit/s
•
128 kBit/s
•
512 kBit/s
•
2048 kBit/s
64 kBit/s
Prot. interf.1
_:5161:1
Prot. interf.1:Mode
•
off
•
on
on
_:5161:105
Prot. interf.1:Max. error
rate per hour
0.000 % to 100.000 %
1.000 %
_:5161:106
Prot. interf.1:Max. error
rate per min
0.000 % to 100.000 %
1.000 %
_:5161:107
Prot. interf.1:Disturbance
alarm after
0.05 s to 2.00 s
0.10 s
_:5161:108
Prot. interf.1:Transm. fail.
alarm after
0.0 s to 6.0 s
6.0 s
_:5161:109
Prot. interf.1:Delay time
threshold
0.1 ms to 30.0 ms
30.0 ms
_:5161:110
Prot. interf.1:Difference Tx
and Rx time
0.000 ms to 3.000 ms
0.100 ms
_:5161:113
Prot. interf.1:PPS synchroni-
zation
•
telegr. and PPS
•
telegr. or PPS
•
PPS sync. off
PPS sync. off
Ext. Synchron.
_:9181:114
Ext. Synchron.:PPS pulse
loss alarm aft.
2.1 s to 60.0 s
2.1 s
Information List
No.
Information
Data Class
(Type)
Type
Device combin.
_:5131:52
Device combin.:Behavior
ENS
O
_:5131:53
Device combin.:Health
ENS
O
_:5131:301
Device combin.:Status of topo. recog.
ENS
O
_:5131:302
Device combin.:Topology is
ENS
O
_:5131:303
Device combin.:Devices form
ENS
O
_:5131:304
Device combin.:Number of detect. dev.
INS
O
_:5131:305
Device combin.:Fct. logoff device 1
SPS
O
_:5131:306
Device combin.:Fct. logoff device 2
SPS
O
_:5131:307
Device combin.:Fct. logoff device 3
SPS
O
_:5131:309
Device combin.:Fct. logoff device 4
SPS
O
_:5131:310
Device combin.:Fct. logoff device 5
SPS
O
_:5131:311
Device combin.:Fct. logoff device 6
SPS
O
_:5131:312
Device combin.:Device 1 available
SPS
O
_:5131:313
Device combin.:Device 2 available
SPS
O
3.5.2.11
System Functions
3.5 Protection Communication
SIPROTEC 5, High-Voltage Bay Controller, Manual
127
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...