Function Blocks of the Disconnector
Table 6-10
Function Blocks of the Disconnector Function Group
Function
Block
Description
Parameters
Function
Discon-
nector
The disconnector represents
the physical switch in the
SIPROTEC 5 device.
Maximum output time
Seal-in time
Switching-device type
The disconnector replicates
the switch position from the
status of the binary inputs
and also transmits the
command via the binary
outputs.
Control
Command processing
Control model
SBO time-out
Feedback monitoring time
Check switching authority
Check if pos. is reached
Check double activat.
blk.
Command checks, commu-
nication with the command
source and with the func-
tion block Disconnector
Inter-
locking
Switchgear interlocking
protection
Interlocking condition (deposited
in CFC)
The Interlocking function-
ality generates the releases
for switchgear interlocking
protection.
The setting values of the parameter can be found in the chapter
6.2.3.2 Application and Setting Notes
Additional Settings of Disconnector Switching Element
The settings of the disconnector are assigned to the function blocks on the basis of their relevance. Additional
disconnector settings that cannot be directly assigned to one of the 3 function blocks and are identical to the
circuit-breaker settings are available:
Table 6-11
Setting Options of the Controllable
Command with Feedback
in the
Control
Function
Block of the Circuit Breaker
Characteristics
Function
To Be Found in
Software filtering time
Software filtering time for position
detection
Position of the Control
(1)
function
block
Retrigger filter
(yes/no)
Switching retriggering of the
filtering time on/off by changing
the position
Position of the Control
(1)
function
block
Message time before
filtering
(yes/no)
Consideration of the hardware
filtering time for position-detection
time stamp
Position of the Control
(1)
function
block
Suppress intermediate
position
(yes/no)
When activated,only the inter-
mediate position is suppressed by
the duration of the software
filtering time.
Position of the Control
(1)
function
block
Control Functions
6.2 Switching Devices
SIPROTEC 5, High-Voltage Bay Controller, Manual
327
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...