If external close commands are possible (actuation of the circuit breaker by other devices), which are not
intended to prompt detection of a manual closure, this can be ensured in 2 ways:
•
The input signal is connected in such a way that it is not activated in the event of external close
commands.
•
The external close command is connected to the blocking input
>Block manual close
for manual
closure detection.
Parameter: Action time
•
Recommended setting value
(_:101) Action time
=
300 ms
In order to ensure independence from manual activation of the input signal, the detection function is
extended for a defined length of time using the parameter
Action time
.
Siemens recommends an action time of
300 ms
.
Parameter: CB open dropout delay
•
Default setting
(_:102) CB open dropout delay
=
0 ms
With the
CB open dropout delay
parameter, you can maintain the effectiveness of internal indication
CB
open-circuited
for the set time. If the input signal
>Input
becomes active after external delayed manual
closure, the indication
(_:300) Detected
is output as long as the dropout delay is active.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Manual close
_:101
Manual close:Action
time
0.01 s to 60.00 s
0.30 s
_:102
Manual close:CB open
dropout delay
0.00 s to 60.00 s
0.00 s
Information List
No.
Information
Data Class
(Type)
Type
Manual close
_:6541:501
Manual close:>Block manual close
SPS
I
_:6541:500
Manual close:>Input
SPS
I
_:6541:300
Manual close:Detected
SPS
O
5.5.9.3
5.5.9.4
Function-Group Types
5.5 Function-Group Type Circuit Breaker, 3-Pole
226
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...