Application and Setting Notes
Parameter: Delay failure indication
•
Recommended setting value
(_:6) Delay failure indication
=
5.00 s
Set the
Delay failure indication
parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided. Siemens recommends using the default setting.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Supv. ph.seq.I
_:1
Supv. ph.seq.I:Mode
•
off
•
on
•
test
off
_:6
Supv. ph.seq.I:Delay
failure indication
0.00 s to 100.00 s
5.00 s
Information List
No.
Information
Data Class
(Type)
Type
Supv. ph.seq.I
_:82
Supv. ph.seq.I:>Block function
SPS
I
_:54
Supv. ph.seq.I:Inactive
SPS
O
_:52
Supv. ph.seq.I:Behavior
ENS
O
_:53
Supv. ph.seq.I:Health
ENS
O
_:71
Supv. ph.seq.I:Failure
SPS
O
Trip-Circuit Supervision
Overview of Functions
The Trip-circuit supervision function recognizes disruptions in the trip circuit. When 2 binary inputs are used,
the function recognizes all disruptions in the trip circuit. If only 1 binary input is available, it will not recognize
disruptions at the circuit breaker.
The control voltage for the circuit breaker must be greater than the sum of the minimum voltage drops at the
binary inputs V
Ctrl
> 2 V
BImin
. At least 19 V are required for each binary input. This makes the supervision usable
only with a system-side control voltage of > 38 V.
Structure of the Function
The trip-circuit supervision is integrated into the Circuit-breaker function group. Depending on the number of
available binary inputs, it works with 1 or 2 binary inputs.
[dwtcsueb-010313-01.tif, 1, en_US]
Figure 8-27
Structure/Embedding of the Function
8.3.10.4
8.3.10.5
8.3.10.6
8.3.11
8.3.11.1
8.3.11.2
Supervision Functions
8.3 Supervision of the Secondary System
968
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...