Confirmation ID
Meaning
Description
Switching Authority
Release for switching
authority Local
The confirmation ID is queried only for devices
without a key switch; otherwise it is replaced with
the key switch position.
The confirmation IDs are preset with the following values:
•
Set/operate 222222
•
Control (process, interlocked) 333333
•
Control (not-interlocked) 444444
•
Switching authority local 666666
If you have configured a device with key switches, the confirmation IDs for non-interlocked switching and
switching authority are not displayed or editable in DIGSI; the function is handled by the position of the key
switch.
To increase security, change these codes with DIGSI.
Switching Mode (Interlocked/Non-Interlocked)
The switching mode determines whether or not the switchgear interlocking that has been configured in the
CFC is checked before the command is output.
You can change the switching mode with the key switch S1 (interlocking off/normal). For devices without a
key switch, you can change the switching mode with a corresponding menu item on the display (after
entering a confirmation ID). You can also set the switching mode for switching commands from the sources
DIGSI, station or remote.
!
DANGER
If the switching mode = non-interlocked, the switchgear interlocking protection is shut off
Erroneous switching operations can lead to severe or fatal injuries.
²
Ensure manually that all checks have been implemented.
In addition, you can set the switching mode directly with a binary input or CFC. Use the General function
block (see next figure).
[scmoscha-260511-01.tif, 1, en_US]
Figure 6-27
Switching Mode in Function Block General
The following table shows the effects of changing the switching mode to use command checks.
Control Functions
6.3 Control Functionality
336
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...