The following figure shows 2 application scenarios of protection devices with the Underfrequency load shed-
ding function.
[dw_UFLS_positive power direction, 1, en_US]
Figure 7-164
Application Scenarios
Dotted arrow: Standard forward direction of the protection functionality
Solid arrow:
Positive active-power flow direction
The standard forward direction of the protection functionality is from the busbar to the protected object which
is the transformer for device 1 or the feeder for device 2. The standard forward direction of the protection
functionality is configured via the
(_:8881:116) Neutr.point in dir.of ref.obj
parameter of the
measuring point I-3ph (see chapter
5.1.5 Application and Setting Notes for Measuring Point Current 3-Phase
forward direction of the protection functionality, such as for device 1. To adapt the function to this condition,
the
Positive power direction
parameter is used. With the
Positive power direction
parameter,
you can set the positive active-power flow direction either to the same as or to the inverse of the standard
forward direction.
•
For device 1, set the
Positive power direction
parameter to
inv. to CT neu.pnt sett.
.
Then, the positive active-power flow direction of the power criterion is opposite to the standard forward
direction of the protection functionality. Consequently, the Underfrequency load shedding function
sheds the medium-voltage busbar when the positive power-flow direction is from the high-voltage
busbar to the medium-voltage busbar.
•
For device 2, set the
Positive power direction
parameter to
acc. to CT neu.pnt sett.
.
Then, the positive active-power flow direction of the power criterion is the same as the standard forward
direction of the protection functionality. Consequently, the Underfrequency load shedding function
sheds the feeder when the positive power-flow direction is from the medium-voltage busbar to the
feeder.
Protection and Automation Functions
7.20 Underfrequency Load Shedding
SIPROTEC 5, High-Voltage Bay Controller, Manual
839
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...