Adjustment of Application Templates/Functional Scope
Application Template
The application template defines the preconfigured functional scope of the device for a specific use case. A
certain number of application templates is predefined for each device type. DIGSI 5 automatically offers the
application templates for selection when a new device is installed. The available application templates with
the respective functional scope are described in more detail in
The selection of the application template first predefines which function groups and functions are present in
the device.
You can adjust the functional scope to your specific application.
Adjusting the Functional Scope
Adjust the functional scope based on the selected application template. You can add, copy or delete functions,
tripping stages, function blocks, or complete function groups.
In the DIGSI 5 project tree, this can be done via the following Editors:
•
Single-line configuration
•
Information routing
•
Function settings
Siemens recommends the Single-line configuration Editor to adjust the functional scope.
Complete missing functionalities from the Global DIGSI 5 Library. Then, the default settings of the added func-
tionality are active. You can copy within a device and between devices as well. Settings and routings are also
copied when you copy functionalities.
i
i
NOTE
If you delete a parameterized function group, function, or level from the device, all settings and routings
will be lost. The function group, function, or tripping stage can be added again, but then the default
settings are active.
In most cases, the adjustment of the functional scope consists of adding and deleting functions, tripping
stages, and function blocks. As previously described, the functions, tripping stages, and function blocks auto-
matically connect themselves to the measuring points assigned to the function group.
In few cases, it may be necessary to add a protection or circuit-breaker function group. These newly added
function groups do not contain (protection) functions. You must individually load the (protection) functions
for your specific application. You must also connect the protection or circuit-breaker function group to one or
more measuring points (see chapter
2.1 Function Embedding in the Device
). You must connect newly added
protection function groups to a circuit-breaker function group (see chapter
).
Functions, tripping stages, function blocks, and function groups can be added up to a certain maximum
number. The maximum number can be found in the respective function and function-group descriptions.
Function Points
Function points (FP) are assigned to specific functions, but not to other functions. Further information can be
found in the description of application templates, in the chapter
.
The device is supplied with the acquired function-point credit. Functions with function points can be loaded
into the device only within the available function-point credit. The functional scope cannot be loaded into the
device if the required number of points of the functional scope is higher than the function-point credit. You
must either delete functions or upgrade the function-point credit of the device.
No function points are required to add additional stages in functions.
Extending the Function-Point Credit
You can reorder function points if the function-point credit for the device is not enough.
2.2
Basic Structure of the Function
2.2 Adjustment of Application Templates/Functional Scope
38
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...