The following applies for the power consumption of the equivalent resistance R:
[fofr1b04-090330-01.tif, 1, en_US]
Application and Setting Notes
Parameter: Alarm delay
•
Recommended setting value
(_:100) Alarm delay
=
2 s
(Trip-circuit supervision with 2 binary
inputs)
•
Recommended setting value
(_:100) Alarm delay
=
300 s
(Trip-circuit supervision with 1 binary
input)
With the parameter
Alarm delay
, you can set the time for the delayed output of the indication
Trip-
circuit failure
.
For Trip-circuit supervision with 2 binary inputs, you set the
Alarm delay
parameter so that the short-
term transient states do not cause the function to activate.
For the Trip-circuit supervision with 1 binary input, you set the
Alarm delay
so that the longest duration
of a trip command is bridged without fail. This ensures that the indication is emitted only if the trip circuit is
actually interrupted.
Parameter: Blk.by trip/open cmd from
•
Possible settings, application-dependent
The parameter works only with the trip-circuit supervision with 1 binary input.
Use the parameter
Blk.by trip/open cmd from
to set the conditions under which the trip-circuit super-
vision is blocked. The following conditions can cause a blocking of the trip-circuit supervision function:
•
The
Trip/open cmd.
of the circuit breaker is activated.
•
One of the trip commands of the circuit-breaker failure protection is activated.
•
One of the trip commands of the circuit-breaker reignition protection is activated.
The circuit-breaker failure protection is set to protect a different trip circuit than the local circuit breaker. Using
the configuration options of the
Blk.by trip/open cmd from
parameter, multiple trip-circuit supervision
functions can be operated in parallel. For instance, a trip-circuit supervision function dedicated to a local
circuit breaker can also be operated parallel to a higher-level circuit breaker upon which the circuit-breaker
failure protection acts.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
74TC sup.1BI #
_:1
74TC sup.1BI #:Mode
•
off
•
on
•
test
on
_:100
74TC sup.1BI #:Alarm delay
1.00 s to 600.00 s
300.00 s
_:102
74TC sup.1BI #:Blk.by trip/
open cmd from
Setting options depend on
configuration
8.3.11.5
8.3.11.6
Supervision Functions
8.3 Supervision of the Secondary System
SIPROTEC 5, High-Voltage Bay Controller, Manual
973
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...