This parameter is used to set the frequency difference for switching over between synchronous and asynchro-
nous operation.
Siemens recommends using the default setting of
0.01 Hz
.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:5041:1
Sychr./Asycr.1:Mode
•
off
•
on
•
test
off
_:5041:101
Sychr./Asycr.1:Min. oper-
ating limit Vmin
0.300 V to 340.000 V
90.000 V
_:5041:102
Sychr./Asycr.1:Max.
operat. limit Vmax
0.300 V to 340.000 V
110.000 V
_:5041:110
Sychr./Asycr.
1:Max.durat.
sync.process
0.00 s to 3600.00 s; ∞
30.00 s
_:5041:108
Sychr./Asycr.1:Direct
close command
•
no
•
yes
no
_:5041:126
Sychr./Asycr.1:Voltage
adjustment
0.500 to 2.000
1.000
De-en.gized switch.
_:5041:105
Sychr./Asycr.1:Close
cmd. at V1< & V2>
•
no
•
yes
no
_:5041:106
Sychr./Asycr.1:Close
cmd. at V1> & V2<
•
no
•
yes
no
_:5041:107
Sychr./Asycr.1:Close
cmd. at V1< & V2<
•
no
•
yes
no
_:5041:103
Sychr./Asycr.1:V1, V2
without voltage
0.300 V to 170.000 V
5.000 V
_:5041:104
Sychr./Asycr.1:V1, V2
with voltage
0.300 V to 340.000 V
80.000 V
_:5041:109
Sychr./Asycr.1:Supervi-
sion time
0.00 s to 60.00 s
0.10 s
Asynchr. op.mode
_:5041:114
Sychr./Asycr.1:Async.
operating mode
•
off
•
on
on
_:5041:113
Sychr./Asycr.1:CB make
time
0.01 s to 0.60 s
0.06 s
_:5041:115
Sychr./Asycr.1:Max.
voltage diff. V2>V1
0.000 V to 170.000 V
5.000 V
_:5041:116
Sychr./Asycr.1:Max.
voltage diff. V2<V1
0.000 V to 170.000 V
5.000 V
_:5041:117
Sychr./Asycr.1:Max.
frequency diff. f2>f1
0.000 Hz to 4.000 Hz
0.100 Hz
_:5041:118
Sychr./Asycr.1:Max.
frequency diff. f2<f1
0.000 Hz to 4.000 Hz
0.100 Hz
Synchr. op.mode
_:5041:119
Sychr./Asycr.1:Sync.
operating mode
•
off
•
on
on
_:5041:120
Sychr./Asycr.1:f-
threshold ASYN<->SYN
0.010 Hz to 0.200 Hz
0.010 Hz
6.4.8.3
Control Functions
6.4 Synchronization Function
386
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...