Characteristics
Function
To Be Found in
Spontaneous position
changes filtered by
(Gen.
Software Filt./Spont. Software Filt.)
If the
General software
filter
setting is selected, the
general settings for software
filtering of spontaneous position
changes and for position changes
caused by a switching command
apply. By selecting
Spontaneous
software filter
, a separate
filtering is activated for sponta-
neous position changes.
Position of the Control
(1)
function
block
Spontaneous software
filter time
Software filtering time for sponta-
neous position changes
Position of the Control
(1)
function
block
Spontaneous retrigger
filter
(yes/no)
Switching on/off retriggering of the
filtering time by spontaneous posi-
tion change
Position of the Control
(1)
function
block
Spontaneous indication
timestamp before filtering
(yes/no)
Consideration of the hardware
filtering time for position-detection
time stamp in case of a sponta-
neous change
Position of the Control
(1)
function
block
Spontaneous suppress
intermediate position
(yes/no)
When activated, only the sponta-
neous change to the intermediate
position is suppressed by the dura-
tion of the software filtering time.
Position of the Control
(1)
function
block
(1)
First click Position and then the Details key in the Properties window (below).
Table 6-12
Setting Options of the Controllable
Position
in the Disconnector Function Block (Chatter
Blocking)
Characteristics
Function
To Be Found in
Chatter blocking
(yes/no)
Switching chatter blocking on/off
Position of the Disconnector
(1)
function block
(1)
First click Position and then the Details key in the Properties window (below).
Table 6-13
Additional Settings in the Device Settings with effect on the Disconnector
Characteristics
Function
To Be Found in
Number of permissible
state changes
Chatter-blocking setting value:
Once for the entire device
Device settings (to be found under
Settings)
Chatter test time
Number of chatter tests
Chatter dead time
Chatter test time
The inputs and outputs as well as the setting options of the Disconnector switch function block are described
in the next chapter (see
6.2.3.3 Trigger Variants of the Disconnector
). The Control function block is described
identically as the Circuit-breaker function block, with the exception that the command check blocking is avail-
able through protection only with the circuit breaker.
More information on this is can be found in chapter
6.2.2.2 Application and Setting Notes
Interlocking
The
Interlocking
function block generates the releases for switchgear interlocking protection. The actual
interlocking conditions are deposited in CFC. For more information on this, see section Chapter
6.3.1 Command Checks and Switchgear Interlocking Protection
.
Control Functions
6.2 Switching Devices
328
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...