Resetting the Thermal Map
You can reset the thermal memory via the binary input indication
>Reset thermal replica
. The thermal
memory will then have a 0 value. A reparameterization will also lead to resetting the thermal memory.
Blocking the Function
Blocking will cause a picked up function to be reset. The function can be blocked externally or internally by the
binary input signal
>Block stage
.
All indications then drop out and the thermal memory is set to the value 0.
Blocking Closure
The signal
Block close
can be used to prevent closure of the protected object at a high thermal load. The
signal is set if the tripping overtemperature is exceeded, and cancelled if the temperature falls below the
dropout threshold.
Functional Measured Values
Measured Value
Description
(_:310) Equival. current
Besides the thermal measured values in percent, the equivalent
current is also issued as a thermal current-measured value (A or
kA). The current equivalent is the primary current, which corre-
sponds to the thermal measured value in percent, assuming
steady-state conditions.
(_:304) Time until close
The
Time until close
is the expected time until it is possible
for the protected object for reclosure. The calculation of this
value is based on the assumption of constant currents. The
thermal replica has then fallen below the setting value of the
dropout threshold.
(_:305) Time until trip
The
Time until trip
is the expected time until tripping
(100 % value exceeded) occurs. The calculation of this value is
based on the assumption of constant currents.
(_:306) Overload
The value
Overload
indicates the current temperature of the
protected object in percent. Tripping occurs if 100 % is exceeded.
Application and Setting Notes
Parameter: Threshold current warning
•
Recommended setting value
(_:101) Threshold current warning
=
1.1 A
for l
rated
= 1 A
Set the threshold to the maximum permissible continuous current (I
max, perm
). This results in the same setting
value as for
K-factor
.
Parameter: Threshold thermal warn.
•
Recommended setting value
(_:104) Threshold thermal warn.
=
90 %
The default setting can be left at a
K-factor
of 1.1, because the thermal memory sets itself to 83 % at
continuously flowing rated current. The calculation uses the rule of three: 100 % corresponds to (
K-factor
)
2
and x % corresponds to 1
2
.
[fowarnsc-100810-01.tif, 2, en_US]
At a
K-factor
of 1.05, the thermal memory for rated current is 91% filled. Increase the
Threshold
thermal warn.
to 95%.
7.27.4
Protection and Automation Functions
7.27 Thermal Overload Protection, 1-Phase
896
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...