Addr.
Parameter
C
Setting Options
Default Setting
_:14011:112
90V V.contr.2w:Target
voltage 1
10.000 V to 340.000 V
110.000 V
_:14011:157
90V V.contr.2w:Target
voltage 2
10.000 V to 340.000 V
110.000 V
_:14011:158
90V V.contr.2w:Target
voltage 3
10.000 V to 340.000 V
110.000 V
_:14011:159
90V V.contr.2w:Target
voltage 4
10.000 V to 340.000 V
110.000 V
_:14011:113
90V V.contr.2w:Band-
width
0.2 % to 10.0 %
1.0 %
_:14011:114
90V V.contr.2w:T1 char-
acteristic
•
Linear
•
Inverse
Linear
_:14011:115
90V V.contr.2w:T1 delay
5 s to 600 s
40 s
_:14011:116
90V V.contr.2w:T1
Inverse Min
5 s to 100 s
5 s
_:14011:117
90V V.contr.2w:T2 delay
0 s to 100 s
5 s
_:14011:118
90V V.contr.2w:Fast step
up
•
off
•
on
off
_:14011:119
90V V.contr.2w:Fast step
up limit
-50.0 % to 0.0 %
-6.0 %
_:14011:120
90V V.contr.2w:Fast step
up T delay
0.0 s to 10.0 s
2.0 s
_:14011:121
90V V.contr.2w:Fast step
down
•
off
•
on
on
_:14011:122
90V V.contr.2w:Fast step
down limit
0.0 % to 50.0 %
6.0 %
_:14011:123
90V V.contr.2w:Fast step
down T delay
0.0 s to 10.0 s
0.0 s
_:14011:124
90V V.contr.2w:Function
monitoring
0 min to 120 min
15 min
_:14011:155
90V V.contr.2w:Regulate
with T2 at start
•
off
•
on
on
_:14011:160
90V V.contr.2w:Set
point mode active
•
off
•
on
on
Parallel operation
_:14011:161
90V V.contr.2w:Parallel
mode
•
No mode
•
Master
•
Follower
•
Circulat. react current
No mode
_:14011:168
90V V.contr.2w:Parallel-
transfomer id
1 to 8
1
_:14011:164
90V V.contr.2w:Parallel
mode changeable
•
by setting
•
controllable
by setting
_:14011:165
90V V.contr.2w:Force
master changeable
•
by setting
•
controllable
by setting
_:14011:166
90V V.contr.2w:Maximal
tap difference
1 to 9
2
_:14011:169
90V V.contr.2w:Reactive
I control factor
0.01 to 100.00
1.00
_:14011:146
90V V.contr.2w:VT
supervision
•
off
•
on
on
Control Functions
6.9 Voltage Controller
502
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...