The default setting is a reasonable value. Siemens recommends using the default setting.
Stage Description
Description
Logic of the Stage
[lo_load shedding_stage, 1, en_US]
Figure 7-165
Logic Diagram of the Underfrequency Load Shedding Stage
Pickup and Operate
If the following 3 conditions are all fulfilled, a
Pickup
indication is issued:
•
The frequency value drops below the
Threshold
.
•
The
Blocking
input from the function block General is inactive.
•
The preceding 2 conditions are fulfilled during the configured number of frequency measurement cycles
(cycle time = 10 ms). You can set the number with the parameter
f< stabilization counter
.
7.20.4
7.20.4.1
Protection and Automation Functions
7.20 Underfrequency Load Shedding
SIPROTEC 5, High-Voltage Bay Controller, Manual
841
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...