i
i
NOTE
With the
P, Q sign
parameter in the function block General, the sign of the following measured values
of the respective function group can be inverted (see Chapter
Structure of the
Function, section Inversion of Output-Related Measured and Statistical Values):
•
Minimum/maximum values of the active and reactive power:
Min:Ptotal, Max:Ptotal, Min:Qtotal, Max:Qtotal
•
Minimum/maximum values of the average values of the active and reactive power:
AverageMin:Ptotal, AverageMax:Ptotal, AverageMin:Qtotal, AverageMax:Qtotal
Application and Setting Notes for Minimum/Maximum Values
The minimum/maximum values functionality is not preconfigured. If you want to use the functionality, you
must load it from the library into the respective function group.
The following settings listed for the calculation of the minimum/maximum values can be set with DIGSI or at
the device. You find the setting parameters in DIGSI in the project tree under Settings > Device settings.
Parameter: Min/Max cyclic reset
•
Default setting:
(_:107) Min/Max cyclic reset
=
yes
Parameter Value
Description
Yes
Cyclical resetting of the minimum and maximum value memories is activated
No
Cyclical resetting of the minimum and maximum value memories is deactivated
None of the following parameters are visible
Parameter: Min/Max reset each
•
Default setting:
(_:108) Min/Max reset each
=
1 day
Parameter Value
Description
1 day to 365 days
Resetting of the minimum value and the maximum value, cyclically on all specified
days, for example each day (1 day)
Parameter: Min/Max reset minute
•
Default setting:
(_:109) Min/Max reset minute
=
0 min
Parameter Value
Description
0 min to 1439 min
Resetting the minimum value and the maximum value at the specified minute of the
day, which is stated in the parameter
Min/Max Reset takes place every
, for
example 0 min (= 00:00)
Parameter: Min/Max days until start
•
Default setting:
(_:110) Min/Max days until start
=
1 day
:
Parameter Value
Description
1 day to 365 days
Indication of when the cyclical reset procedure of the minimum values and
maximum values begins, for example in 1 day (after the parameterization)
9.8.2
Measured Values, Energy Values, and Supervision of the Primary System
9.8 Minimum/Maximum Values
SIPROTEC 5, High-Voltage Bay Controller, Manual
1041
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...