Operational Measured Values
The operational measured values are not preconfigured in the Voltage-current 1-phase function group. You
can instantiate them in the function group or delete them from the function group. You can find the opera-
tional measured values in the DIGSI library, in the folder FG Voltage-current 1-phase under Measurements
→ Operational values.
[scui1pom, 1, en_US]
Figure 5-12
Operational Measured Values
Table 5-3
Operational Measured Values of the Voltage-Current 1-Phase Function Group
Measured Values
Primary
Secondary
% Referring to
I
1-phase current
A
A
Parameter
Rated operating current
V
12
1-phase voltage
kV
V
Parameter
Rated operating voltage
V
N
13
Residual Voltage
kV
V
Parameter
Rated operating
voltage
/√3
V
0
14
Zero-sequence voltage
kV
V
Parameter
Rated operating
voltage
/√3
f
Frequency
Hz
Hz
Parameter
Rated frequency
P
Active power
MW
W
Parameter
Rated apparent power
Q
Reactive power
Mvar
var
Parameter
Rated apparent power
You can find the parameters
Rated operating current
,
Rated operating voltage
, and
Rated
apparent power
in the General function block of the Voltage-current 1-phase function group. You can
find the parameter
Rated frequency
in the General function block of the Device settings.
i
i
NOTE
The frequency can be calculated from the voltage or current measured value.
The active and reactive power are only displayed if the voltage and the 1-phase current are connected to
the function group. If the connected voltage is a phase-to-ground voltage (VA, VB, VC) or any voltage Vx,
the specific power values are displayed. Otherwise the power is displayed as not available.
Application and Setting Notes
i
i
NOTE
Prior to creation of the protection functions in the function group, these functions should first be
connected to the appropriateCircuit-breaker function group.
5.3.3
12
V is only visible if it is connected to a 1-phase voltage measuring point.
13
VN is only visible if it is connected to a 3-phase voltage measuring point of the type 3 ph-to-gnd volt. + VN or 3 ph-to-ph volt. + VN.
14
V0 is only visible if it is connected to a 3-phase voltage measuring point of the type 3 ph-to-gnd voltages.
Function-Group Types
5.3 Function-Group Type Voltage/current 1-Phase
SIPROTEC 5, High-Voltage Bay Controller, Manual
203
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...