With the parameter
Enable filter
, you set whether the Filter is enabled.
Parameter Value
Description
yes
If gained RMS values should be used in one of the protection stages, set
parameter
Enable filter
=
yes
.
no
If no gained RMS values are needed, set the parameter
Enable filter
=
no
.
Parameter:
h(0)
,
h(1)
,
h(2)
,
h(3)
,
h(4)
•
Default setting
(_:2) h(0)
=
0.000
•
Default setting
(_:3) h(1)
=
0.000
•
Default setting
(_:4) h(2)
=
0.000
•
Default setting
(_:5) h(3)
=
0.000
•
Default setting
(_:6) h(4)
=
1.000
With the default value of the coefficients, the filter has no effect and no gain is applied.
If the filter shall be applied to adapt the RMS value calculation to a specific protection object such as a reactor,
the reactor manufacturer has to provide the required amplitude response (gain factors) for the reactor. To
determine the coefficients h(0) to h(4) for the FIR filter, you must enter the gain factors into the auxiliary PC
tool which is available in the SIPROTEC download area. The 5 required coefficients are generated by the tool.
They have to be entered manually as settings to configure the filter. The amplitude attenuation of higher
frequencies due to the anti aliasing filter of the device is automatically taken into account and compensated
by the filter.
To only compensate the attenuation of higher frequencies by the device, set the following coefficients in the
filter.
Rated Frequency
Filter Coefficients for Only Compensating the Device Amplitude Attenu-
ation
50 Hz
h(0) = -0.002
h(1) = -0.012
h(2) = 0.045
h(3) = -0.110
h(4) = 1.151
60 Hz
h(0) = -0.005
h(1) = -0.020
h(2) = 0.058
h(3) = -0.128
h(4) = 1.170
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Filter
_:1
Filter:Enable filter
•
no
•
yes
no
_:2
Filter:h(0)
-100.000 to 100.000
0.000
_:3
Filter:h(1)
-100.000 to 100.000
0.000
_:4
Filter:h(2)
-100.000 to 100.000
0.000
_:5
Filter:h(3)
-100.000 to 100.000
0.000
_:6
Filter:h(4)
-100.000 to 100.000
1.000
7.26.3.3
Protection and Automation Functions
7.26 Thermal Overload Protection, 3-Phase - Advanced
880
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...