Parameter: Release threshold
•
Recommended setting value
(_:101) Release threshold
=
0.5 A
for I
rated
= 1 A or
2.5 A
for I
rated
= 5 A
The
Release threshold
parameter is used to set the lower limit of the maximum phase current (I
max
).
Parameter: Delay failure indication
•
Recommended setting value
(_:6) Delay failure indication
=
5.00 s
Set the
Delay failure indication
parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Supv. balan. I
_:1
Supv. balan. I:Mode
•
off
•
on
•
test
off
_:101
Supv. balan. I:Release
threshold
1 A @ 100 Irated 0.030 A to 35.000 A
0.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
2.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
0.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
2.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
2.500 A
_:102
Supv. balan. I:Threshold
min/max
0.10 to 0.95
0.50
_:6
Supv. balan. I:Delay
failure indication
0.00 s to 100.00 s
5.00 s
Information List
No.
Information
Data Class
(Type)
Type
Supv. balan. I
_:82
Supv. balan. I:>Block function
SPS
I
_:54
Supv. balan. I:Inactive
SPS
O
_:52
Supv. balan. I:Behavior
ENS
O
_:53
Supv. balan. I:Health
ENS
O
_:71
Supv. balan. I:Failure
SPS
O
Current-Sum Supervision
Overview of Functions
In healthy system operation, the sum of all currents at one measuring point must be approximately 0. The
Current-sum supervision function monitors the sum of all currents of one measuring point in the secondary
circuit. It detects connection errors during commissioning or short circuits and interruptions in the secondary
circuit.
For summation of the currents, the device requires the phase currents and the ground current of the current
transformer neutral point or of a separate ground-current transformer at this measuring point. Select the
following connection variant:
•
Current-transformer connections connected to 3 current transformers and the neutral point (see
in the Attachment)
8.3.8.5
8.3.8.6
8.3.9
8.3.9.1
Supervision Functions
8.3 Supervision of the Secondary System
962
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...