[loveranw-100311-01.tif, 1, en_US]
Figure 7-9
Processing the Starting Signals of the CBFP
Current-Flow Criterion
The current-flow criterion is the primary criterion for determining the circuit-breaker switch position. A circuit-
breaker pole is supposed to be closed, and the current-flow criterion fulfilled, as soon as one of the phase
currents exceeds the phase-current threshold value and a plausibility current exceeds the associated threshold
value at the same time. The plausibility current can be either a 2nd phase current (to compare with the phase-
current threshold value) or the zero-sequence or negative-sequence current (to compare with the sensitive
threshold value). The additional evaluation of the plausibility current increases the safety of the criterion.
In the case of ground faults, the sensitive threshold value can be dynamically applied to the phase currents as
well. The current-flow criterion is fulfilled when the currents exceed the sensitive threshold value. The phase-
current threshold value is then ineffective. The binary signal
>Threshold sensitive
is used for the switch-
over.
If you set the
3I0 criterion
parameter to
Direct release
, you prevent the plausibility check of the
zero-sequence current. In this way, a pickup only by way of this current can be achieved. With the
Threshold
3I0 dir. release
parameter, you set the threshold value to be exceeded.
If you set the
I2 criterion
parameter to
Direct release
, you also switch off the plausibility check of
the negative-sequence current. With the
Threshold I2 dir. release
parameter, you set the threshold
value to be exceeded.
If you set the
I2 criterion
parameter to
Direct release
, plausibility is checked via the phase currents
with 1/3 *
Threshold I2 dir. release
.
The measuring algorithm is optimized for fast dropout when the value drops below the threshold value.
The following figure shows an example for the logic for the current-flow criterion with 3-pole circuit breaker.
With the 1/3-pole circuit breaker, the activation signal of the current-flow criterion is phase-selective.
Protection and Automation Functions
7.1 Circuit-Breaker Failure Protection
522
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...