Directional Time-Overcurrent Protection, Ground
Setting Values for the Function Direction Determination
Method for direction determination
Zero sequence
Negative sequence
–
Minimum V0 or V2 threshold
0.150 V to 20.000 V
0.001 V
Rotation angle of the reference voltage
-180° to 180°
1°
Forward range
0° to 180°
1°
Setting Values for All Stage Types
Direction mode
Forward
Reverse
–
Method of measurement
Fundamental component
RMS value
–
Threshold value
1 A @ 50 and 100 Irated
0.030 A to 35.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.15 A to 175.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.030 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.15 A to 8.000 A
Increments of 0.001 A
Setting Values for Stage Type Definite Time-Overcurrent Protection
Dropout ratio
0.90 to 0.99
Increments of 0.01
Operate delay
0.00 s to 60.00 s
Increments of 0.01 s
Dropout delay
0.00 s to 60.00 s
Increments of 0.01 s
Setting Values for Stage Type Inverse Time-Overcurrent Protection (IEC/ANSI)
Type of characteristic curve
Characteristic curves according to IEC and ANSI
Dropout
Disk emulation
Instantaneous
–
Time multiplier
0.00 to 15.00
Increments of 0.01
Minimum time of the curve
0.00 to 1.00 s
Increments of 0.01 s
Additional time delay
0.00 to 60.00 s
Increments of 0.01 s
Dropout Values for Stage Type Inverse Time-Overcurrent Protection (IEC/ANSI)
Disk emulation
Approx. 0.90 * threshold value
Instantaneous
Approx. 1.05 * threshold value
Approx. 0.95 * pickup value
Characteristic Curves for Stage Type Inverse Time-Overcurrent Protection (IEC/ANSI)
Standard Characteristic Curves According to IEC
Normal inverse: type A
Refer to the respective picture of the technical data for the non-
dir-OC-ground function
11.9.2 Stage with Inverse-Time Charac-
Very inverse: type B
Extremely inverse: type C
Long-time inverse
Standard Characteristic Curves According to ANSI/IEEE
11.11
Technical Data
11.11 Directional Time-Overcurrent Protection, Ground
1136
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...