Under the following conditions, the
Default temperature
will be set as ambient temperature:
•
A temperature sensor for measuring the ambient temperature is not connected.
•
The temperature measurement is interrupted and the measured temperature value is less than the
Default temperature
.
Siemens recommends using the default setting.
Parameter: Minimal temperature
•
Default setting
(_:117) Minimal temperature
=
-20°C
If the measured ambient temperature drops below the preset value, the set value will be assumed as the
ambient temperature. If the overload protection works with a prespecified outside temperature, and this
temperature drops below the value set in the
Minimal temperature
parameter, the
Minimal tempera-
ture
can also be used.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
49 Th.overl. #
_:1
49 Th.overl. #:Mode
•
off
•
on
•
test
off
_:2
49 Th.overl. #:Operate &
flt.rec. blocked
•
no
•
yes
no
_:101
49 Th.overl. #:Threshold
current warning
1 A @ 100 Irated 0.030 A to 35.000 A
1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A
5.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.000 A
5 A @ 50 Irated
0.15 A to 175.00 A
5.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
5.000 A
_:104
49 Th.overl. #:Threshold
thermal warn.
50 % to 100 %
90 %
_:105
49 Th.overl. #:Dropout
threshold operate
50 % to 99 %
90 %
_:106
49 Th.overl. #:K-factor
0.10 to 4.00
1.10
_:110
49 Th.overl. #:Thermal
time constant
10 s to 60000 s
900 s
_:107
49 Th.overl. #:Imax
thermal
1 A @ 100 Irated 0.030 A to 10.000 A
2.500 A
5 A @ 100 Irated 0.15 A to 50.00 A
12.50 A
1 A @ 50 Irated
0.030 A to 10.000 A
2.500 A
5 A @ 50 Irated
0.15 A to 50.00 A
12.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
2.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
12.500 A
_:109
49 Th.overl. #:Tempera-
ture rise at Irated
40 K to 200 K
70 K
_:113
49 Th.overl. #:Storage of
thermal replica
•
no
•
yes
no
_:114
49 Th.overl. #:Behav. at
I> Imax therm.
•
current limiting
•
freeze therm. rep.
current limiting
_:118
49 Th.overl. #:Default
temperature
-55°C to 55°C
40°C
7.27.5
Protection and Automation Functions
7.27 Thermal Overload Protection, 1-Phase
900
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...