The following setting example shows how you can change the transformer ratio in DIGSI 5, and what impact
this has on the settings in the setting views Primary and Secondary. The protection setting is observed in the
example of the Overcurrent protection function.
The following output data are assumed:
Current transformer:
1000 A/1 A
Protection pickup value:
1.5 A
The following figure shows the protection setting of the Overcurrent protection function in the secondary
view. The threshold value of the stage is set to 1.5 A.
[scmodsek_1, 1, en_US]
Figure 3-92
Protection Setting, Display of the Active Setting Sheet
When you click the green arrow in the setting sheet at the upper left, you get to the window for switching
over to the setting view (see the following figure). Select the setting view you prefer.
[scmodums_2, 1, en_US]
Figure 3-93
Switchover to the Desired Setting View
The following figures show the setting sequence in the Primary edit mode. Set the transformer data. In the
example, the current transformer has a transformation ratio of 1000 A/1 A.
System Functions
3.9 General Notes for Setting the Threshold Value of Protection Functions
SIPROTEC 5, High-Voltage Bay Controller, Manual
155
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...