Up to 50th harmonic, f
rated
= 50 Hz
2 % of the setting value or 10 mA (I
rated
= 1 A)
or 50 mA (I
rated
= 5 A), (f
rated
± 10 %)
Up to 50th harmonic, f
rated
= 60 Hz
3 % of the setting value or 20 mA (I
rated
= 1 A)
or 100 mA (I
rated
= 5 A), (f
rated
± 10 %)
Currents, method of measurement = RMS value
with filter for the gain of harmonics (including compensation of the amplitude attenuation
45
(33 % harmonics, in relation to the fundamental component)
Up to 30 harmonic
1.5 % of the setting value or 10 mA (I
rated
= 1 A)
or 50 mA (I
rated
= 5 A), (f
rated
± 10 %)
46
Up to 50th harmonic, f
rated
= 50 Hz
3% of the setting value or 20 mA (I
rated
= 1 A)
or 100 mA (I
rated
= 5 A), (f
rated
± 10 %)
47
Up to 50th harmonic, f
rated
= 60 Hz
4 % of the setting value or 20 mA (I
rated
= 1 A)
or 100 mA (I
rated
= 5 A), (f
rated
± 10 %)
48
Operate time for 2 ≤ I/I threshold value ≤ 20
5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Dropout time for I/I threshold value ≤ 0.90
5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Time delays
1 % of the setting value or 10 ms
Influencing Variables for Thresholds
Transient excess pickup in method of measurement =
fundamental component, for τ > 100 ms (with
complete unbalance)
< 5 %
Stage with User-Defined Characteristic Curve
Setting Value for the Function Block Filter
h(0)
-100.000 to 100.000
Increments of 0.001
h(1)
-100.000 to 100.000
Increments of 0.001
h(2)
-100.000 to 100.000
Increments of 0.001
h(3)
-100.000 to 100.000
Increments of 0.001
h(4)
-100.000 to 100.000
Increments of 0.001
Setting Values for Protection Stage
Method of measurement
Fundamental component
RMS value
–
Threshold value
1 A @ 50 and 100 Irated
0.030 A to 35.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.15 A to 175.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
Increments of 0.001 A
11.8.3
45
In case that the filter response exactly matches the user-defined gain factors
46
In case that the user-defined gain factor is set below 3. The tolerance increases, if the gain factor is larger.
47
In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.
48
In case that the user-defined gain factor is set below 7. The tolerance increases, if the gain factor is larger.
Technical Data
11.8 Overcurrent Protection, Phases
1120
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...