Configurability
The motor-starting log is only present in the Motor function group. There is no column for the motor-starting
log in the DIGSI information routing. The entries in the motor-starting log are preconfigured and cannot be
changed.
Saving and Deleting the Logs
Deleting the logs of the device in the operating state is unnecessary. If storage capacity is no longer sufficient
for new indications, the oldest indications are automatically overwritten with new incoming events. In order
for the memory to contain information about the new faults in the future, for example, after an inspection of
the system, a deletion of the log makes sense. Resetting the logs is done separately for the various logs.
i
i
NOTE
Before you delete the content of a log on your SIPROTEC 5 device, save the log with DIGSI 5 on the hard
disk drive of your PC.
i
i
NOTE
Not all logs of your SIPROTEC 5 device can be deleted. These limitations apply especially to logs with rele-
vance for security and after-sales (security log, device-diagnosis log, setting-history log).
i
i
NOTE
Upon deletion of the fault log, the associated fault records are also deleted. In addition, the meters for fault
number and fault-record number are reset to 0. In contrast, if you delete fault records, the content of the
fault log, including the allocated fault numbers, remains.
i
i
NOTE
If the device executes an initial start, for example, after an update of the device software, the following
logs are automatically deleted:
•
Operational log
•
Fault log
•
Ground-fault log
•
Setting-history log
•
User log
•
Motor-startup log
Back up the deletable logs using DIGSI 5.
i
i
NOTE
If a ground fault is currently active, the ground-fault log cannot be deleted.
Deleting Logs on the On-Site Operation Panel
•
To reach the selected log from the main menu, use the navigation keys of the on-site operation panel
(example operational log):
Main Menu → Indications → Operational log
3.1.6
System Functions
3.1 Indications
68
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...