Settings
Addr.
Parameter
C
Setting Options
Default Setting
Control
_:101
Control:Control model
•
status only
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:102
Control:SBO time-out
0.01 s to 1800.00 s
30.00 s
_:103
Control:Feedback moni-
toring time
0.01 s to 1800.00 s
1.00 s
_:104
Control:Check switching
authority
•
no
•
yes
yes
_:105
Control:Check if pos. is
reached
•
no
•
yes
yes
_:106
Control:Check double
activat. blk.
•
no
•
yes
yes
_:107
Control:Check blk. by
protection
•
no
•
yes
yes
Information List
No.
Information
Data Class
(Type)
Type
Control
_:53
Control:Health
ENS
O
_:58
Control:Cmd. with feedback
DPC
C
6.3.4
6.3.5
Control Functions
6.3 Control Functionality
SIPROTEC 5, High-Voltage Bay Controller, Manual
359
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...